Cabinet & Equipment-Room Power System

Cabinet & Equipment-Room Power System

The HJ-DYZ-600 intelligent high-frequency switch-mode power system comprises a cabinet, AC distribution, rectifier modules (up to 12 fully configured), a monitoring module, and DC distribution. It offers comprehensive battery management—including low-voltage protection and optional load disconnect—plus temperature compensation, automatic voltage regulation, stepless current limiting, capacity calculation, online battery testing, and sleep energy-saving. Networked design with RS232/RS485 and dry-contact ports enables flexible networking, remote monitoring, and unattended operation, with full AC/DC surge protection and complete fault protection/alarm functions.
Product Features
Fully digital: Fully digital interleaved PFC innovative control with limited bipolar ZVS full-bridge topology, current-doubler rectifier topology, and dual MCUs for fully digital monitoring;
Lower operating cost: Rectifiers use PFC so AC input current matches the voltage waveform and phase; high system efficiency saves energy and reduces OPEX;
Higher efficiency: High-frequency PWM conversion reduces switching losses and EMI, allowing installation inside switching equipment rooms;
Intelligent monitoring & management: Intelligent battery management with continuously settable equalization/float voltages and charge current limits via controller or remote system; supports float, equalization, and battery testing;
High compatibility: Equipotential design across the cabinet improves EMC and lightning protection;
Contact Us

Product Parameters

Environmental Parameters Operating conditions Transport conditions Storage conditions Applicable standards Remarks
Category Parameter Unit
Climatic conditions Temperature Low temperature ℃ -33 -40 -40 YD/T 1058-2000 Clauses 4.1.1 and 4.1.2 Full-load start at −40℃; linear 20% derating from +55 to +65℃.
High temperature ℃ 65 70 70
Temperature change ℃/min / 1 / ETS 300 019-2-2 T2.3
Operating ambient temperature ℃ -33—65 Full-load extreme operating temperature
Storage temperature ℃ -40—70
Humidity Relative humidity % 5-90 90 (40±2℃) / YD/T 1058-2000 Clause 4.1.3 Short-term test: 0—95%, max 95%, non-condensing
Condensation Yes/No No No Yes
Atmospheric pressure Low pressure kPa 86 70 70 YD/T 1058-2000 Clause 4.1.4 Module testing only
High pressure kPa 106 106 106
Altitude m ≤4000 Above 2000 m, derate 0.5℃ per additional 100 m