Product Parameters
| 300A Basic Configuration | |
| AC input | 220 Vac |
| System max. capacity | 300A (up to 6 × 50A rectifier modules) |
| Load branches | Standard: load disconnect 100A×3 (breakers), battery disconnect 100A×2 (breakers) (load branches configurable per need, max. 10 branches) |
| Battery branches | 125A ×2 circuits (breakers) |
| AC input switch | 125AP × 1 circuit (single-phase) |
| AC surge protection | 20 kA (Max 40 kA) |
| Optional configuration | |
| AC output branch | 10A×1 |
| AC maintenance outlet | 10A×1 |
| Temperature sensing cable | Ambient temperature sensor cable ×1 |
| DC surge protection | 15 kA×1 |
| Dimensions & weight | |
| Dimensions (mm) | 550 (W)×280 (D)×550 (H) |
| Weight (kg) | 38 (including 6 rectifier modules) |
| 200A Basic Configuration | |
| AC input | 220 Vac |
| System max. capacity | 200A (up to 4 × 50A rectifier modules) |
| Load branches | Load disconnect: 100A×1, 63A×2, 32A×2, 20A×2 (breakers); battery disconnect: 20A×1, 10A×2 (breakers) (load branches configurable per need, max. 10 branches) |
| Battery branches | 125A ×2 circuits (breakers) |
| AC input switch | 80AP × 1 circuit |
| AC surge protection | 20 kA (Max 40 kA) |
| Optional configuration | |
| AC output branch | 10A×1 |
| AC maintenance outlet | 10A×1 |
| Temperature sensing cable | Ambient temperature sensor cable ×1 |
| DC surge protection | 15 kA×1 |
| Dimensions & weight | |
| Dimensions (mm) | 480 (W)×270 (D)×465 (H) |
| Weight (kg) | 24 (including 4 rectifier modules) |