| DC Side Parameters |
| Cell Type |
LFP 3.2V/314Ah |
| Energy Rating |
261kWh |
| Combined Configurations |
1P260S |
| Voltage Range |
728-936V DC |
| Number Of Cycles |
≥6000 @25℃ |
| Depth of Discharge |
90%DOD |
| Communication Interface |
Modbus TCP,Modbus RTU,CAN2.0 |
| Grid-connected output parameters |
| Rated output power |
125kW |
| Rated grid voltage |
230/400V,3L+N+PE |
| Max current |
198A |
| Power factor |
0.99 |
| Rated grid Freq. |
50/60Hz |
| Total Harmonic Current Distortion |
< 2%(rated power) |
| Off-grid output parameters |
| Rated output power |
125kW |
| Rated Output voltage |
230V/400V |
| Rated grid Freq. |
50/60Hz |
| Max output current |
198A |
| Off-grid switching time |
20ms |
| Efficiency |
| Maximum efficiency |
99.00% |
| System parameter |
| Dimensions (H * D * W) |
1055*2300*1300 |
| Weights |
≈2.8T |
| Ingress Protection Grade |
IP54 |
| Corrosion Resistance Class |
C4 |
| Operating Temperature Range |
charge:0℃~55℃(32 °F~131 °F)discharge:-20℃~55℃ (-4 °F~131 °F) |
| Operating humidity range |
5%~95%(No Condensing) |
| Cooling method |
Liguid cooling |
| Fire Fighting Methods |
Aerosol Suppression at Pack Level |
| Max. operating altitude |
≤2000 m |
| Communication Protocol |
Modbus TCP,Modbus RTU,CAN2.0 |
| Certification Standards |
| Safety certification |
IEC62619/IEC63056/IEC62477 |
| EMC certification |
CE |
| Grid Connection Standard |
EN 50549-1/10 |