| Product Model |
HJ-H16-H08 (k-1) |
| Photovoltaic Parameters |
| Maximum Input Power [W] |
12000 |
| Maximum Input Voltage [V] |
590 |
| Operating Voltage Range / Rated Voltage [V] |
80~500/360 |
| Maximum Input Current [A] |
16/16 |
| Maximum Short-circuit Current [A] |
20/20 |
| Number of MPPT |
2 |
| Number of Strings per MPPT |
1/1 |
| AC Parameters (Grid-Connected) |
| Rated Output Power [W] |
8000 |
| Maximum Apparent Output Power [VA] |
8800 |
| Maximum Input Power [W] |
8800 |
| Rated Voltage [Vac] |
230, L/N/PE |
| Rated Frequency [Hz] |
50/60 |
| Maximum Output Current [A] |
34.8 |
| Power Factor Range |
~1 (0.8 leading to 0.8 lagging can be set) |
| Current Total Harmonic Distortion (@Rated Power) [%] |
< 3 |
| AC Parameters (Off-Grid) |
| Rated Output Power [W] |
8000 |
| Maximum Apparent Output Power [VA] |
8800 |
| Rated Output Voltage [Vac] |
230, L/N/PE |
| Rated Output Frequency [Hz] |
50/60 |
| Peak Output Apparent Power [VA] (60s) |
8400 |
| Peak Output Apparent Power [VA] (10s) |
9000 |
| Grid-Grid Switching Time [ms] |
< 10 |
| AC Parameters (Diesel Generator Input) |
| Rated Voltage [Vac] |
230, L/N/PE |
| Rated Frequency [Hz] |
50/60 |
| Rated Input Apparent Power [VA] |
8000 |
| Battery Parameters |
| Operating Voltage Range [V] |
306~408 |
| Battery Model |
|
| Rated Charge/Discharge Current [A] |
25/25 |
| Maximum Charge/Discharge Current [A] |
30/30 |
| Number of Batteries |
4 |
| Single Battery Capacity [kWh] |
4.096 |
| Rated Capacity [kWh] |
16.384 |
| Usable Capacity [kWh] |
14.75 |
| Efficiency |
| Standard Ambient Temperature System Efficiency [%] |
88% |
| Basic Parameters |
| Operating Temperature Range [℃] |
-25~60 (>45 derating) |
| Operating Altitude [m] |
< 4000 |
| Protection Rating |
IP65 |
| Relative Humidity Range [%] |
0~95, no condensation |
| Dimensions (W*H*D) [mm] |
425*340*1750 |
| Certification Standards |
| Certification Standards |
IEC62109-1/-2 |
| Safety Standards |
EN61000-6-1/-3, IEC61000 |
| EMC Standards |
AS4777.2:2020, NRS097-2-1:2017, EN 50549-1 for Czech, VDE-AR-N 4105:2018, EN50549-1:2019+AC:2, G98 G99, OVE- |